Basic Info.
Product Description
cUL Certificate Electric PVC copper wire Nmd90 14/2 12/2 14/3 12/3 Indoor Non-Metallic Solid Conductor with Ground electrical Wire 300V Canada
Applications:
NMD90 cables may be used for both exposed work in dry locations or concealed work in dry or damp locations.
The maximum allowable conductor temperature is 90°C. The minimum recommended installation temperature is -25°C for two-conductor cables and -10°C for three-conductor cables (with suitable handling procedures). Material should be properly stored above 0°C for 24 hours prior to installation.
The maximum voltage rating for all intended applications is 300 volts. Consult the Canadian Electrical Code1 for further information related to applications.
Standards:
Type NMD90 cable complies with:
ASTM
CSA C22.2 No. 48 (non-metallic sheathed cable)
Canadian Electrical Code1
CONSTRUCTION:
NMD90 cables are available as two- or three-conductor cables with a bare grounding conductor. It is manufactured using annealed (soft) copper conductors-compressed standing for stranded conductors; a heat-resistant thermoplastic polyvinyl chloride (PVC) insulation and nylon jacket for the individual conductors with a PVC jacket for the overall construction.
Conductors are white, black and red (for 3 conductor cables). Cable jackets are colour coded by size for quick identification in the Table below:
JACKET COLOUR CODE - Typical Application Guide
•WHITE - General Residential Wiring
•RED - 2 Black and Red conductors - 208V-240V Circuits (no neutral)
•ORANGE - No. 10 AWG General Residential Wiring
•YELLOW - No. 12 AWG General Residential Wiring
•BLUE - No. 14 AWG - 2 black and white conductors - 120V Arc Fault Circuit Interupter Applications
NMD90 jackets which reduces the coefficient of friction, allowing cables to be installed without external
lubricants, resulting in reduced labour and materials costs.
Specification:
AWG OR KCMIL | STRAND | NOMINAL INSULATION THICKNESS INCH/MM | NOMINAL JACKET THICKNESS INCH/MM | NOMINAL OVERALL DIAMETER INCH/MM | CABLE WEIGHT LBS/KFT KG/KM | ||||
14 | 1 | 0.015 | 0.38 | 0.004 | 0.10 | 0.11 | 2.79 | 15 | 22 |
12 | 1 | 0.015 | 0.38 | 0.004 | 0.10 | 0.12 | 3.05 | 23 | 34 |
10 | 1 | 0.020 | 0.51 | 0.004 | 0.10 | 0.15 | 3.81 | 37 | 54 |
14 | 19 | 0.015 | 0.38 | 0.004 | 0.10 | 0.11 | 2.79 | 16 | 24 |
12 | 19 | 0.015 | 0.38 | 0.004 | 0.10 | 0.13 | 3.30 | 24 | 36 |
10 | 19 | 0.020 | 0.51 | 0.004 | 0.10 | 0.17 | 4.32 | 39 | 58 |
8 | 19 | 0.030 | 0.76 | 0.005 | 0.13 | 0.22 | 5.59 | 63 | 94 |
6 | 19 | 0.030 | 0.76 | 0.005 | 0.13 | 0.26 | 6.60 | 98 | 145 |
4 | 19 | 0.040 | 1.01 | 0.006 | 0.15 | 0.33 | 8.38 | 157 | 234 |
3 | 19 | 0.040 | 1.01 | 0.006 | 0.15 | 0.36 | 9.14 | 193 | 287 |
2 | 19 | 0.040 | 1.01 | 0.006 | 0.15 | 0.39 | 9.91 | 240 | 357 |
1 | 19 | 0.050 | 1.27 | 0.007 | 0.18 | 0.43 | 10.92 | 300 | 446 |
1/0 | 19 | 0.050 | 1.27 | 0.007 | 0.18 | 0.47 | 11.94 | 376 | 560 |
2/0 | 19 | 0.050 | 1.27 | 0.007 | 0.18 | 0.52 | 13.21 | 467 | 695 |
3/0 | 19 | 0.050 | 1.27 | 0.007 | 0.18 | 0.57 | 14.48 | 581 | 864 |
4/0 | 19 | 0.050 | 1.27 | 0.007 | 0.18 | 0.64 | 16.26 | 724 | 1077 |
250 | 37 | 0.060 | 1.52 | 0.008 | 0.20 | 0.69 | 17.53 | 855 | 1272 |
300 | 37 | 0.060 | 1.52 | 0.008 | 0.20 | 0.76 | 19.30 | 1022 | 1521 |
350 | 37 | 0.060 | 1.52 | 0.008 | 0.20 | 0.79 | 20.07 | 1191 | 1772 |
400 | 37 | 0.060 | 1.52 | 0.008 | 0.20 | 0.85 | 21.59 | 1345 | 2001 |
500 | 37 | 0.060 | 1.52 | 0.008 | 0.20 | 0.94 | 23.88 | 1668 | 2482 |
600 | 61 | 0.070 | 1.78 | 0.009 | 0.23 | 1.10 | 27.94 | 1994 | 2967 |
750 | 61 | 0.070 | 1.78 | 0.009 | 0.23 | 1.16 | 29.46 | 2465 | 3668 |